Connect an eWON Flexy to an Omron NJ & NX1P

In this video, Brad Vorrie walks you through the process of connecting an eWON Flexy to an Omron NJ and NX1P. For the first step let’s take a look at setting up the NJ and NX1P. Open your project in Sysmac Studio. The eWON can currently communicate with an Omron FINS driver over TCP or UDP, utilizing CJ memory variables. For the NJ your default FINS settings should get you communicating, so no additional communication setup is required. On the NX1P, Under Operation Settings and FINS Setting, note the value of your Local Network. In my example, it is 2. Now, decide what tags you want to monitor and associate those tags to CJ memory. If you are using an NX1P, be sure the CJ memory values are enabled under memory settings. Now, go to your global tags, and under the AT column, enter